Arc Monitor ZELK-3

When an electrical arc occurs in switchgears it can cause thermal damage to equipment and injury to personnel. The damages are directly proportional to the arc burning time. Arc monitor ZELK-3 rapidly recognizes electrical arc and disconnects the circuit breaker in order to disconnect feeding of the arc. By using maximum 18 optical sensor for arc detection and two static output arc monitor performs nonselective or section selective switchgear protection instantaneously in less than 1ms, which is negligible in comparison with disconnection time of circuit breaker. That feature enables early arc recognition, and greatly decreases possible damages.

Arc protection system gives high contribution in protection of personnel and equipment with low price and simple application. Because of that a lot of European producers of medium and low voltage switchgears with air insulation apply devices for arc protection.

[showhide type=”opis” more_text=”Show more” less_text=”Show less”]

  • high speed tripping (in less than 1ms)
  • monitoring of max. 18 optical detectors
  • functionality 250ms after auxiliary power supply failure
  • AC or DC auxiliary power supply
  • local and remote indication of power supply failure and tripping
  • indication of fault location on digital display
  • two static outputs
  • static outputs can be supplied with AC or DC supply
  • galvanical insulation 2,5kV betveen all insulated circuits
  • small dimensions and simple mounting on rail DIN EN 50022-35
  • ZELK-3 in combination with SM is optimal solution for non selective or section selective switchgear protection

 
Catalogues are available to the registered users only

[restrict]

leaflet
[/restrict]
[/showhide]

Back to top