Voltage Sensors NS-20 and Current Sensors SS-30
- IEL
- Product groups
- Monitoring, control and protection – smart grids
- Switchgear remote control
- Voltage Sensors NS-20 and Current Sensors SS-30
Monitoring control and protection – smart grids
- Substation remote control (switchyard) 10(20)/0,4 kV
- Intelligent electronic devices IED
- Monitoring and Control Terminal UST-10Gc
- Info Terminal IT-1
- Monitoring and Control Terminal UST-3
- Monitoring and Control Terminal UST-4
- Monitoring and Control Terminal UST-10G
- Input Output Unit DIO 16-8
- Feeder Terminal TP-10
- Measuring Terminal MT-10SQ
- Measuring Terminal MT-20S
- Measuring Terminal MT-30S
- Measuring Terminal MT-40
- Measuring Terminal MT-40S
- Preamplifier PP-10
- Uninterruptible power supply system BN-15
- Uninterruptible power supply system BN-20
- Uninterruptible power supply system BN-30
- Switchgear remote control
- Ground fault and short circuit detection and indication in cable grids
- Ground fault and short circuit detection and indication in overhead grids
- Communication equipment
NS-20 Voltage Sensors and SS-30 Current Sensors are used as fault detectors in insulated or grounded overhead grids within the system for remote control of switch disconnectors, e.g. Remote Terminals DT-20RN. The Voltage Sensors NS-20 consist of a non-conventional voltage elements (capacitive dividers) and are used to measure the voltages UL1, UL2, UL3. Voltage Sensor is distributed in the medium voltage cable connector and the IK-20S Fault Indicator, and via the PK terminal box and the cable it is connected to the Fault Indicator embedded in the disconnecting switch Remote Terminal. SS-30 Current Sensors are simply mounted on the insulators of cable connectors and are used to measure the currents IL1, IL2, IL3.
IK-20S Fault Indicator is an intelligent electronic unit that accepts current signals from three SS-30 Current Sensors and voltage signals from six SS-20 Voltage Sensors, and processes and detects a ground fault and short circuit in an insulated or grounded overhead grid. Short circuit detection is based on current measurement, and detection of a directional ground fault is determined by transient analysis of residual current and voltage.
- simple mounting and connection of the SS-30 sensor on the medium voltage cable connector insulators
- voltage sensors NS-20 integrated in test connection on medium voltage cable connector
- detection of short circuit and ground fault in an isolated or grounded overhead grid
- measurement of disconnecting switches IL1, IL2, IL3 and UL1, UL3, UL3 with connection to IK-20S Fault Indicator
- external installation, from -40 ° C to + 55 ° C
Current Sensors SS-30
- rated primary current 50 … 400 A
- accuracy of current measurement ± 0.5%, 10 P25
Voltage Sensors NS-20
- accuracy of the voltage measurement ± 3%